RFC 1628, "UPS Management Information Base", May 1994

Source of RFC: upsmib (ops)
See Also: RFC 1628 w/ inline errata

Errata ID: 4831
Status: Verified
Type: Technical
Publication Format(s) : TEXT

Reported By: Sean Van Gorder
Date Reported: 2016-10-14
Verifier Name: Benoit Claise
Date Verified: 2016-10-28

Section 4 says:

       OBJECT     upsOutputSource
       SYNTAX     INTEGER {
           normal(2),
           battery(4)
       }
       DESCRIPTION
               "Support of the values other(1), none(2), bypass(4),
               booster(6) and reducer(7) is not required."

It should say:

       OBJECT     upsOutputSource
       SYNTAX     INTEGER {
           normal(3),
           battery(5)
       }
       DESCRIPTION
               "Support of the values other(1), none(2), bypass(4),
               booster(6) and reducer(7) is not required."

Notes:

This error appears 3 separate times, in the MODULE-COMPLIANCE definitions upsSubsetCompliance, upsBasicCompliance, and upsFullCompliance.

The wrong numbers are specified with the named values, which must match the OBJECT-TYPE definition of upsOutputSource.