RFC Errata
RFC 1628, "UPS Management Information Base", May 1994
Source of RFC: upsmib (ops)See Also: RFC 1628 w/ inline errata
Errata ID: 4831
Status: Verified
Type: Technical
Publication Format(s) : TEXT
Reported By: Sean Van Gorder
Date Reported: 2016-10-14
Verifier Name: Benoit Claise
Date Verified: 2016-10-28
Section 4 says:
OBJECT upsOutputSource SYNTAX INTEGER { normal(2), battery(4) } DESCRIPTION "Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required."
It should say:
OBJECT upsOutputSource SYNTAX INTEGER { normal(3), battery(5) } DESCRIPTION "Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required."
Notes:
This error appears 3 separate times, in the MODULE-COMPLIANCE definitions upsSubsetCompliance, upsBasicCompliance, and upsFullCompliance.
The wrong numbers are specified with the named values, which must match the OBJECT-TYPE definition of upsOutputSource.