RFC Errata
RFC 1628, "UPS Management Information Base", May 1994
Source of RFC: upsmib (ops)See Also: RFC 1628 w/ inline errata
Errata ID: 3276
Status: Verified
Type: Technical
Publication Format(s) : TEXT
Reported By: Jürgen Sellinath
Date Reported: 2012-07-03
Verifier Name: Ron Bonica
Date Verified: 2012-07-03
Section 4.8 says:
upsShutdownAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off. Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off. When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect. On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any upsShutdownAfterDelay already in effect."
::= { upsControl 2 }
upsStartupAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
It should say:
upsShutdownAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off. Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off. When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect. On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any upsShutdownAfterDelay already in effect."
::= { upsControl 2 }
upsStartupAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
Notes:
The upper limit of the ranges of upsShutdownAfterDelay and upsStartupAfterDelay points to the intention to use a 32-bit signed integer.
The biggest positive value of a 32-bit singed integer, however, is 2147483647. On a 32-Bit system the upper range given within RFC1628 (2147483648) is so large that is is unsigned, which conflicts with the limitation to 32 bits.
As 2147483648 seconds is more than 68 years, it seems preferable to change this to 2147483647, loosing 1 second but gaining the ability to be implemented with 32 bits.